| BEFORE |
AFTER |
|
|
| Finding Date |
: 2026-07-28 |
| SBI AC / HAC |
: L62-RM1.P4 |
| Description |
: QUICK FIX. Pressure sealing air fan P4 agak tinggi sekitar 40 mbar |
| Category |
: Operation |
| C/L/T |
: T |
| SGA Action |
: Adjust bukaan damper hingga pressure sekitar 36 mbar |
| Status |
: Done |
| Standardize |
: Pressure sealing air fan normal operasi sekitar 33-36 mbar |
| Reporter |
: MUHAMMAD HABIB GINANJAR JAYA |